Home About Us Skip Navigation Links
Job Reference Skip Navigation Links
Request Quote Send PO Contact Us
 
 

Copper Conductors Data

Conductor Diameter Sectional Area Composition Resistance Current Conductor Diameter Sectional Area Composition Resistance Current
AWG mm mm2 No./mm Ohm/Km A AWG mm mm2 No./mm Ohm/Km A
36 0.127 0.012 1/0.127 1426 0.1 18 1.02 0.823 1/1.024 23 5
                  7/0.404    
34 0.16 0.02 1/0.160 899 0.2       16/0.254    
                       
32 0.203 0.032 1/0.203 578 0.3 16 1.29 1.31 1/1.290 14.7 8
                  7/0.488    
30 0.254 0.05 1/0.254 350 0.4       26/0.254    
      7/0.102           65/0.160    
                       
28 0.32 0.08 1/0.320 232 0.5 15 1.39 1.51 7/0.52 11.2 9
      7/0.127           30/0.254    
                       
26 0.4 0.128 1/0.404 146 0.8 14 1.63 2.08 1/1.630 8.79 11
      4/0.203           7/0.615    
      7/0.160           41/0.254    
                       
24 0.5 0.205 1/0.511 89.2 1.4 12 2.05 3.31 1/2.050 5.41 20
      7/0.203           19/0.470    
      11/0.160           65/0.254    
                       
22 0.64 0.325 1/0.643 54.8 2 10 2.59 5.261 7/0.978 3.64 25
      7/0.254           19/0.594    
      17/0.160           104/0.254    
                       
20 0.81 0.519 1/0.813 34.5 3 8 3.26 8.36 7/1.23 2.72 34
      7/0.320           37/0.536    
      10/0.254           165/0.254    

 

 
   